Refincor Ammonium Bisulfide
References
78C7.1-01: HYDROCRACKER AND HDS UNIT:
M. C. Flickinger reported on a failure in
an effluent system. They do use continuous wash water injection,
but to lower ammonium bisulfidefrom a typical 5% to
7% concentration to a more desirable 2% level would require
an increase from 284 L/min (75 gal/min) to about 1,136 L/min
(300 gal/min). Their water is condensate with 100 ppb oxygen.
He asked for advice on water wash rates and acceptable oxygen
levels.
78C7.2-01: HYDROCRACKER AND HDS UNIT:
R. L. Piehl responded with an opinion their
oxygen level was too high at 100 ppb. Use of stripped sour
water, instead of condensate, should improve this situation,
if oxygen leaks are avoided. When separator water ammonium
bisulfidelevels are less than 2 wt% to 2-1/2 wt%, problems
are usually nil, but there is no sudden abrupt change because
other factors are also important.
78C7.2-02: HYDROCRACKER AND HDS UNIT:
J. D. McCoy stated that surplus injection
water is needed to avoid full evaporation. McCoy uses 25%
excess water to assure full saturation. Typical wash rates
for McCoy would be 190 to 380 L/min (50 to 100 gal/min) for
a 25,000 to 35,000 BPD unit, whereas W. H. Sharp reported
over 760 L/min (200 gal/min) for a 20,000 BPD unit at 149øC
(300øF) and 10 MPa (1,500 psig).
78C7.2-03: HYDROCRACKER AND HDS UNIT:
E. F. Ehmke agreed too much water shouldn't
erode if gas velocities are less than 6.1 m/s (20 ft/s). Proper
spray nozzles are important for good mixing.
85F8.8-02: HYDROCRACKER AND HDS UNIT:
G. F. Rak said that they have also seen more salt plugging
in their effluent exchangers.
85F8.8-03: HYDROCRACKER AND HDS UNIT:
J. E. Cantwell commented that the problems
might be caused by ammonium hydrosulfide due to lower charge
rates, resulting in lower temperatures in the effluent train.
At higher temperatures, the ammonium hydrosulfide would pass
through the exchangers into the separator. D. R. Clarida agreed
that this was a possibility on some of units in question.
87C7.6-03: HYDRODESULFURIZATION UNIT:
Dannie Clarida, CONOCO, reported a problem
that occurred in their hydrodesulfurizer effluent train, which
had a low rate of continuous water wash at 1/2 gpm/1,000 bbl.
In the process, at those operating conditions, the actual
liquid water was 0.05 to 0.1 gpm/1,000 bbl, making conditions
worse by concentrating corrodents and severe corrosion occurred
in the carbon steel pipe downstream from the injection point
as well as 3 heat exchangers.
87F7.6-01: HYDRODESULFURIZATION UNIT:
Dannie Clarida, CONOCO, asked whether anyone
was having problems with reactor effluent water wash. The
amount of liquid water at temperature can lead to corrosion
if there is only a small quantity present after injection.
88F5.8-01: HYDRODESULFURIZATION UNIT:
D. R. Clarida (Conoco) described a recent
corrosion problem in the bottom of a diesel fractionator downstream
from the separator. Corrosion was in the form of localized,
deep pitting that did not appear to have been caused by deposits.
The material was carbon steel and service temperature was
585øF. What deposits there were consisted of iron sulfide,
iron sulfate, ammonia, and other nitrogen compounds.
89C7.6-07: HYDRODESULFURIZATION UNIT:
R. J. Horvath (Shell) asked what maximum
velocity is being used for alloys in wet ammonium bisulfide
service. He said that they were using 20 fps for CS but there
would be an incentive to go to higher velocities with alloys
in order to reduce costs.
91C9.7-05: HYDRODESULFURIZATION UNIT:
Dick Horvath (Shell) described a recent occurrence,
not totally understood or resolved yet. They've had a localized
corrosion problem in piping and related blistering and HIC
cracking in cat cracker feed hydrotreater vessels at around
1,200 psig. The unit takes a fairly high nitrogen, moderate
sulfur feed. The effluent line is Incoloy. Effluent KP, as
described in the Bob Piehl paper from 1976, is 3 to 4, which
is very corrosive. They elected to minimize wash water and
use alloy. There was some very localized piping corrosion
in the overhead line from the high- pressure low-temperature
(HPLT) separator, and also in the vapor line from the low-pressure
low-temperature (LPLT) separator. Both of these carbon steel
lines had vapor flow velocities of about 40 feet/second with
insignificant corrosion for over twenty years.
With a recent catalyst change in the reactors,
they got more de-nitrification of the feed. Ammonia levels
went up significantly and KPs in these vapor lines tripled.
They ended up with very localized corrosion washout areas,
classic ammonium bisulfide corrosion. In hundreds of
feet of pipe there were a few washout spots the size of a
clenched fist. In the case of the LPLT separator vapor line,
they could explain that they went from a noncorrosive to a
corrosive range, using Piehl's KP. In the case of the HPLT
separator vapor line, even though the ammonia levels had tripled
and the KPs had tripled from 0.02 to 0.06, they still wouldn't
expect a problem. In a discussion with Bob Piehl, he commented
that his KP was derived from an empirical fit of data obtained
years ago from effluent air coolers.
The HPLT area may not be the same conditions;
it doesn't have a lot of water; it is a vapor that's basically
saturated with water and the only water in the line is small
amounts of condensate that accumulates down the line, causing
the localized washouts. They suspect that they went from compositions
below 10% ammonium bisulfidein that condensate to the
15% to 20%. In addition to the piping, they looked at the
separators. In the HPLT separator they had done a thorough
internal inspection and WFMP check in 1988; the vessel was
in excellent shape.
This time there were massive blisters in
the bottom head, about 4" in diameter, ruptured wide enough
to stick a credit card into the rupture. There were a number
of cracks that went down at least 5/8"; most of the HIC damage
was into the plate about 3/4". The head was in the worst condition.
All of the material was A212B. WFMP looked like a Christmas
tree on both sides of welds and on the head-to-shell weld,
with cracking aligned at the toe of the weld both on the shell
can side and on the head side. HIC was so extensive they condemned
the vessel. The LPLT separator also had some cracking, but
they were able to repair that vessel. They feel they went
over a threshold, probably somewhere within that 10% to 15%
ammonium bisulfidelevel. The inspector commented that
they used to have a nice, tight, hard, dense, sulfide scale.
This time it was loose and "fluffy." This scale seems t
Monday, August 15, 2005 12:25 PM
ry little corrosion in the vessels; there was one washout
area about 1/4" deep at an interface level, probably from
a whipping action from the gas inlet.
91C9.7-06: HYDRODESULFURIZATION UNIT:
Joerg Gutzeit (Amoco) asked whether they
could have been seeing under-deposit corrosion, or whether
cyanides were involved.
91C9.7-07: HYDRODESULFURIZATION UNIT:
Dick Horvath (Shell) responded that the spots
were obvious washouts; the scale around them was intact and
the washout areas were devoid of scale. There was almost no
loss at all surrounding the fist-sized washouts. Just downstream
were big, voluminous deposits, in which one could see flow
effects. There was no evidence of cyanide, as indicated by
Prussian blue coloration or sampling and testing.
91C9.7-08: HYDRODESULFURIZATION UNIT:
Joerg Gutzeit (Amoco) had some related comments.
They have several amine unit stripper overheads with a lot
of ammonium bisulfide and KPs as high as 60. Ammonia
levels are around 8%, and H2S is about 5% in the water. 304
SS seems to corrode out and they've gone to 316 SS, which
seems to be holding up.
91C9.7-09: HYDRODESULFURIZATION UNIT:
Don
Monday, August 15, 2005 12:25 PM
ound-color: #ffff90">ammonium bisulfide, not
in terms of KP. They try to keep below 10% in effluent air
coolers. Chevron uses a lot of carbon steel there. They control
velocities, and in the amine stripper overhead reflux line
they try to control the velocities also to 20 feet/second.
91C9.7-10: HYDRODESULFURIZATION UNIT:
Joerg Gutzeit (Amoco) said they also use
% by weight, which is easier to interpret than KP, but they
use 2% as a value that they believe comes closer to Bob Piehl's
KP guidelines.
91C9.7-11: HYDRODESULFURIZATION UNIT:
Don Truax (Chevron) responded that they believe,
as a rule of thumb, that with less than 2% there probably
is no corrosion problem; if you're higher than that, maybe
to 10%, controlling the velocity helps out; if you're a lot
higher than that, you'll get corrosion even if there's no
velocity.
91C9.7-12: HYDRODESULFURIZATION UNIT:
Ara Bagdasarian (UNOCAL) said that they use
8% as their guide in effluent air coolers, but it depends
on the symmetry of the air cooler, piping, etc. All configurations
are not necessarily good with 8%.
91C9.7-13: HYDRODESULFURIZATION UNIT:
John Coombs (Arco) said that their KP criterion
is 0.07, which comes from the Piehl paper. Above this value
they'll alloy. It's a significant point that Dick Horvath's
corrosion occurred at a KP of 0.06. He added that Piehl's
original KP was calculated from table values, whereas the
bisulfide concentration is measured in the field. His concern
was that there may be a difference between calculated and
measured values, possibly because of the problems in getting
good measurements.
91C9.7-14: HYDRODESULFURIZATION UNIT:
Dick Horvath (Shell) has not used KP a lot;
they usually use ammonium bisulfidelevel. Looking at
KPs as a postscript didn't leave them very comfortable. They
measured ammonium bisulfideand historically had not
exceeded 10%, typically around 8% to 11%, but during this
run it was 14% to 16%, which was a significant jump.
92F5.7-05: HYDRODESULFURIZATION UNIT:
Cathy Shargay (ARCO) reported on an HDS unit
where they wanted to reduce the water injected upstream of
the effluent air cooler in the overhead of the hot flash drum
system. They have Incoloy 825 tubes in the air cooler and
825 piping downstream of the water injection point. The concern
is with the carbon steel piping at the outlet of the air cooler.
A mass balance determined that the ammonium bisulfidelevel
was 9.5%. The original design was for 8%. Inspection had not
shown any problems. Two corrosion probes were installed in
1992 in the piping. Wash water rates were increased in expectation
of an increase in denitrification due to a catalyst change
that would increase the level of ammonium bisulfide.
The increased denitrification did not materialize, and they
had 5.8% ammonium bisulfide. Therefore, they reduced
the water rate, which increased the ammonium bisulfide
to about 8.7%. The corrosion probes showed a rate of 6 to
11 mpy, which they consider unacceptably high due to the potential
severity of this type of corrosion. They are now increasing
the water rate and decreasing the ammonium bisulfide
content to about 7.2%. They will continue to monitor and will
optimize the wash water rate using the corrosion probes. The
air cooler outlet piping goes to a cold flash drum. They have
not detected hydrogen activity in the drum, but they do not
have hydrogen probes. She emphasized that the only corrosion
they have seen so far has been on the probes, not in any equipment.
92F5.7-06: HYDRODESULFURIZATION UNIT:
Dick Horvath (Shell) reported a similar situation
in a hydrotreater unit. They saw increased hydrogen activity
in the effluent train separator drum downstream of the air
coolers with about 7 to 7.5% ammonium bisulfide. After
a run, they did not see considerable corrosion or blistering
but found HIC damage. The system is similar to the one Cathy
Shargay described. The effluent flows to a hot flash drum
that operates above the ammonium bisulfide range. The
vapors leave the drum and are water washed before passing
through the air cooler to the carbon steel cold flash drum.
It operates at about 120 to 130øF and 1150 to 1200
psi pressure. They did a fitness-for-purpose analysis and
believed they did not need to make repairs.
94C5.6-13: HYDRODESULFURIZATION UNIT:
Ray Konet (Amoco) - They experienced erratic
readings during UT measurement of cat feed hydrotreater unit
effluent air cooler outlet piping to the trim coolers. The
piping was 12-in. diameter carbon steel and the ammonium
bisulfideKp was 0.8. During a B-scan of the suspect area,
they found a total loss of back reflection which was caused
by blisters in elbows with no general corrosion. Piping was
seamless, and the elbows had been hot bent. The microstructure
showed some banding.
96F5.8-14: HYDRODESULFURIZATION UNIT:
Dannie Clarida (Conoco) described recent
failure in a gas oil hydrodesulfurizer that treats feed for
an FCC unit. There was a leak and a fire at an elbow where
the piping comes off the shell side of the trim cooler before
the high-pressure cold separator (corrosion pretty well localized
to the elbow). The line temperature was approximately 49øC
(120øF) and velocity calculated to be 12 m/s (39 ft/s).
The material was carbon steel and the ammonium bisulfidecontent
in the sour water off the cold separator was 10 wt.%. The
average corrosion rate was estimated at 1.2 mm/y (47 mpy)
over the period from 1990 to 1996 with a rate of 1.4 mm/y
(56 mpy) from 1990 to 1992, 0.15 mm/y (6 mpy) from 1992 to
1994, and an accelerated rate of 1.8 mm/y (69 mpy) over the
20-month period from 1994 to 1996 (average corrosion rate
based on 0.36 cm [0.14 in.] of metal remaining at point of
hole-through). Since start-up the feed rate has increased
from a design of 2,000,000 to 3,600,000 L/d (13,000 to 22,500
BPD) and the nitrogen content of the feed has increased. Together,
these changes increased the ammonium bisulfideconcentration,
but the water wash rate was not changed from the original
design because the pump was too small for an increased rate
and the water wash rate was not evaluated as a part of the
expansion.
96F5.8-15: HYDRODESULFURIZATION UNIT:
Jim Feather (Exxon) described similar problems
in two different hydrotreaters (one lube, the other distillate).
In both cases the location was between the final exchanger
or condenser in the hot separator overhead system and the
cold separator. In the distillate hydrotreater the velocity
was approximately 11 to 12 m/s (35 to 40 ft/s) and the ammonia
bisulfide level was about 10 wt.%. The carbon steel corrosion
rate in a T-piece was found to be approximately 5 mm/y (200
mpy); it didn't leak but was found by inspection. This was
repaired by a weld overlay of Type 316L SS because a similar
area had already been overlaid in a similar manner and the
overlay was found to be in excellent condition. In the lube
hydrotreater the velocity was approximately 11 m/s (35 ft/s)
and the ammonium bisulfide level was about 5.6 wt.%.
The carbon steel corrosion rate was about 3.8 mm/y (150 mpy).
Again, this was something that was caught by inspection because
it was targeted as potentally vulnerable because of the known
high velocities.
97C5.8-19: HYDRODESULFURIZATION UNIT:
Dannie Clarida (Conoco) - described a sensitization
problem that occurred in some seamless ASTM A 312 type 321H
SS FCC feed HDS furnace tubes. The unit was started up in
1985 and revamped in 1989. the tubes were designed for 510̊C
(950̊F), 9.96 MPa (1,430 psig) with an operating skin
temperature of 455̊C (850̊F). The tubes were in
the helical radiant section and had been in service for 87,000
hours, 7 years on hydrogen and 4 years on oil and hydrogen.
On startup in 1996, 14 through-wall cracks were found. The
cracking was determined to be chloride SCC initiated from
the outside. The source of chlorides was refractory debris
and steam in the fire box. Additionally, it was found that
the tubes had a significant amount of sensitization, which
was attributed to the use of the high-temperature solution
anneal temperature of 1,121̊C (2,050̊F), which can
make the material more susceptible to sensitization at the
operating temperature of the tube skin. Some internal cracking
due to polythionic acid SCC was also found, but these cracks
were not through-wall. The coil was replaced with type 321H
SS annealed at 1,065̊C (1,950̊F) followed by a lower-temperature
stabilizing anneal at 885̊C (1,625̊F) for 4 hours.
97C5.9-02: HYDRODESULFURIZATION UNIT:
Dannie Clarida (Conoco) - described a tube
leak problem that occurred in a type 347H SS vertically tubed
recycle gas furnace. In this case, the furnace had hydrotested
with a soda ash solution and an attempt had been made to blow
the tubes dry of residual solution. The furnace was then fired
to dry the tubes. The leakage that occurred was due to chloride
pitting corrosion initiated by residual chloride in the soda
ash solution. The next time the furnace was tested, some holes
were drilled in the "U" bends to remove the residual soda
ash solution.
 |
 |
< <
< click here to go back to the previous page :: |
|